Compare the surface temperature with the dew point of the air touching it. If the surface is at or below the dew point, water forms; if it is above, it stays dry. That is the whole rule, and the calculator above does the comparison and tells you how much margin is left either way.
What is the physical rule for surface condensation?
A surface collects water when its surface temperature (°C / °F) falls at or below the dew point (°C / °F) of the air touching it—for instance, 20°C (68°F) air at 60% RH condenses on anything at or below 12.0°C (53.6°F). Not colder than the air — colder than the dew point. That distinction is the entire subject, and it is why a glass of iced water sweats on a mild day while a window on a freezing one stays clear.
What are the only two ways to stop condensation?
You can stop condensation only by warming the surface above the air's dew point (°C / °F) or by lowering indoor moisture (% RH / g/m³) so the dew point drops below the surface temperature.
Once you see the rule as a comparison between two temperatures, it follows that there are exactly two ways to stop condensation, and every remedy anyone has ever suggested is one of them:
- Raise the surface temperature above the dew point. Better glazing, insulation, moving air across the surface, or simply waiting for the sun.
- Lower the dew point of the air touching it, which means having less water in that air.
Nothing else does anything. Wiping the glass removes today's water and changes neither temperature, which is why it comes back. This is also the honest reason the "how to stop condensation" advice varies so wildly in quality: some of it moves one of these two numbers, and some of it does not.
What does condensation margin (°C / °F) mean?
Condensation margin is T_surface − T_dew in °C or °F: a positive margin means the surface stays dry, while a negative margin (−1°C mist to −10°C runoff) means active condensation.
The figure at the top is the gap between your surface and the dew point.
- Positive — the surface is that many degrees above the dew point, and dry. The larger the number, the more the conditions would have to change before it is not.
- Negative — the surface is below the dew point and already collecting water. The size tells you how aggressively: a surface one degree under gathers a faint mist, one ten degrees under runs.
The second readout, the air-to-dew-point spread, is about the air on its own. When that falls under about a degree the air is saturating everywhere at once, and you get fog rather than condensation.
What happens when the dew point drops below 0°C (32°F)?
When the dew point is below 0°C (32°F) and a surface cools past it, water vapour deposits directly as solid frost rather than liquid dew.
When the dew point is under 0°C the vapour goes directly to ice and what you get is frost rather than dew. The threshold temperature is the same number from the same calculation — the calculator flags it so the wording on the page matches what you will actually see on the surface.
Strictly, saturation vapour pressure over ice differs slightly from over water, so a true frost point is a fraction of a degree different from the dew point computed here. The difference is small enough to be swamped by the accuracy of any humidity reading you are likely to have.
At what indoor % RH do single- and double-pane windows fog up?
At 20°C (68°F) indoor air temperature, single-pane glass at 3.0°C fogs up by 40% RH (6.0°C dew point), whereas double-pane glass at 12.0°C stays clear until indoor humidity reaches 60% RH (12.0°C dew point).
| Indoor Temp (°C / °F) | Indoor RH (% RH) | Air Dew Point (°C / °F) | Single-Pane Glass Temp (°C) | Double-Pane Glass Temp (°C) | Condensation Outcome |
|---|---|---|---|---|---|
| 20°C (68°F) | 30% | 1.9°C (35.4°F) | 3.0°C | 12.0°C | No condensation on either pane |
| 20°C (68°F) | 40% | 6.0°C (42.8°F) | 3.0°C | 12.0°C | Condensation on single pane only |
| 20°C (68°F) | 50% | 9.3°C (48.7°F) | 3.0°C | 12.0°C | Severe condensation on single pane |
| 20°C (68°F) | 60% | 12.0°C (53.6°F) | 3.0°C | 12.0°C | Condensation on both pane types |
| 20°C (68°F) | 70% | 14.4°C (57.9°F) | 3.0°C | 12.0°C | Severe moisture runoff and mold risk |